Internal Evaporative Cooler

ECT10800 CloudCooler

The ECT Internal range of evaporative coolers (CREC units) combine a ventilation system, evaporative cooling, recirculation, filtration and CREC® controls into a single box solution, this design significantly reduces installation costs. ECT units are not suitable for external use and are predominantly used in Data Centre and IT cooling installations.


Warning: Undefined array key "stats" in /home/cloudcoolerco/public_html/wp-content/themes/odin-cloudcooler/app/partials/banner/internal-product.php on line 20

Warning: foreach() argument must be of type array|object, null given in /home/cloudcoolerco/public_html/wp-content/themes/odin-cloudcooler/app/partials/banner/internal-product.php on line 20
01 EcoCooling Control System

The unit is controlled via a touch screen user interface. Functionality includes logging of
performance data and faults, altering of system parameters, a functional test routine and password protection. Software
can be managed through an ESCROW account

02 Dynamic Control

A consistent supply temperature is achieved year round by mixing

03 EU4 Filtration

The airflow is subject to EU4 filtration both at the fresh air intake and at the point of supply.

04 Configuration Options – Plinths

The cooler supplies air through a plinth at its base. The cooler can supply air through grilles in the front, sides or a combination of the two. Sup

Technical Specifications

Dimensions

Installed (on plinth)
2585 x 1304 x 1060 mm
Cabinet (incl. pallet)
2235 x 1350 x 1060 mm
Plinth (incl. pallet)
750 x 1350 x 1050 mm

Weight

Ventilation mode
400 kg
Cooling mode
415 kg
Max at overflow
441 kg
Delivered
Cabinet: 340 kg, Plinth: 70 kg

Electrical Supply

Voltage
3~ 400V 50Hz
Current per phase
Design: 1.7A, Max: 5.6A
Power
Design: 0.9 kW, Max: 3.6 kW
Protection
Integrated isolator switch

Cooling Pads (x4)

Manufacturer
Munters
Material
CELdek® 5090
Saturation Efficiency
85-89%
Dimensions
640 x 870 x 100 mm

Water Requirements (Water Supply)

Water quality
Fresh potable water only
Minimum supply rate
500l/hr minimum
Minimum pressure
1 bar
Maximum pressure
7 bar
Connection
15 mm compression fitting to braided hose c/w adjustable flow restrictor
Control
Ball-valve inlet, Float level probe activated shut off, Optional actuated valves available for frost protection
Compliance
WRAS compliant, Double check valve recommended
Liquid Outlet Temperature
25.5 °C

Water Requirements (Drain)

Capacity
2000 l/hr minimum
Connection offered
1” BSP male thread
Control
Drive Open-Drive Close drain valve

Let’s talk about your cooling challenges